Main testing parameters

Small hall

  • AC testing voltage 50 Hz
    Test transformer: 250 kV, 1 A
  • LI testing voltage 1,2/50 µs
    Impulse generator: 750 kV, 30 kJ

Large hall

  • AC testing voltage 50 Hz
    1 200 kV, 1,2 A
    500 kV, 6 A
    200 kV, 10 A
    250 kV, 1 A
  • LI testing voltage 1,2/50 µs
    Impulse generator: 3 MV, 120 kJ up to 2 600 kV
  • SI testing voltage 250/2500 µs
    Impulse generator: 3 MV, 120 kJ up to 1 600 kV
  • DC testing voltage
    up to 300 kV, 50 mA
  • Pollution and ageing testing
    Salt fog chamber - according to Publication IEC 60507 (up to 250 kV)
    Three salt fog chambers for long duration test up to 50 kV
    Device for tracking wheel test up to 50 kV
  • Mechanical testing
    600 kN / 5m (tension)
    20 kN / 1 m (cantilever)
  • Thermal-mechanical testing
    50 kN / 1,8 m (cantilever)
    250 kN / 2,2 m (tension)
    Temperatures: -85°C +95°C
  • Auxiliary equipment
    Oil tanks - tests of the bushings even under rain
    Artificial rain equipment - according to Publication IEC 60-1
    Device for mechanical (short term and long term) tests of insulators